Floor heating manifold DYNA-if

FLOOR HEATING MANIFOLD

DYNA-if

  • with automatic flow control and flow indication

Specifications:

Manifold bar: Stainless steel AISI 304
Dimensions: DN32 stainless steel profile, 1330 mm² cross sectional area
Connections: 1" female threads on both sides
Supply: Flow indication 0-5.0 l/min
Return: Pre-settable valves with integrated flow controller
• automatic hydronic balancing
• stepless flow adjustment of 30-300 l/h
• differential pressure max. 60 kPA, min. 15 kPA (30-150 l/h) up to 20 kPA (150-300 l/h)
• M30x1.5 mm connecting thread
• with adjustment cap
• actuators can be retrofitted
Outlets: ¾" male threads with Eurocone, distance of 50 mm
Pressure stage/ system: PN6 for heating systems with water quality according to VDI 2035

The set consists of a supply and a return bar. Each manifold bar is additionally delivered with two ½” female threads for vent valves and fill/drain valves. The manifold is pre-assembled in soundproofed holders and packed in a cardboard box with identification labels and installation/setting instructions.